ADAM-4577
1 Port Universal Serial Device Gateway
User's Manual
Zobrazit stránku 0
1 2 3 4 5 6 ... 75 76

Shrnutí obsahu

Strany 1 - ADAM-4577

ADAM-45771 Port Universal Serial Device GatewayUser's Manual

Strany 2 - CE Notification

TablesTable 2-1 ADAM-4577 LED Definition ... 9

Strany 4 - Product Warranty

2 ADAM-4577 User’s Manual1.1 IntroductionThe ADAM-4577 is a peer-to-peer data gatewaybetween RS-232/422/485 and Ethernet interfaces. This unit imme

Strany 5

Chapter 1 Overview 3adjust all settings easily. In addition,the utility provides a securityoption that protects all configuration settings from bei

Strany 6 - Contents

4 ADAM-4577 User’s ManualNetwork: RJ-45Serial: DB-9• Transmission speed: 300 bps to 230 Kbps• Parity bit: odd, even, none, space, mark• Data bit: 5

Strany 7

2Getting StartedChapter

Strany 8

6 ADAM-4577 User’s ManualThis chapter includes an overview of the ADAM-4577 hardwareinstallation procedures. As mentioned in the previous chapter, t

Strany 9

Chapter 2 Getting Started 7The following illustration shows the network architecture as below: Figure 2-1 Network architecture:PollingFigure 2

Strany 10

8 ADAM-4577 User’s Manual Figure 2-3 Network architecture:Peer-to-peerInternetADAM-4577RS-485ADAM-4577RS-485ADAMEthe rnetRS-232 /422/4 85+VsGNDPo

Strany 11 - Overview

Chapter 2 Getting Started 9Table 2-1 ADAM-4577 LED Definition2.1.3 Top / Front / Rear ViewThere are three network status LEDs located on the top

Strany 12 - 1.1 Introduction

Copyright NoticeThis document is copyrighted, 2001, by Advantech Co., Ltd. All rightsare reserved. Advantech Co., Ltd., reserves the right to make imp

Strany 13 - 1.3 Specifications

10 ADAM-4577 User’s ManualFigure 2-6 ADAM-4577—Back PanelFigure 2-4 ADAM-4577—Top PanelFigure 2-5 ADAM-4577—Front PanelStatus/PowerSpeed/LinkTX/RX(E

Strany 14 - 1.4 Package Checklist

Chapter 2 Getting Started 112.1.4 StickersIf you forget the IP addresses of specific ADAM-4577 or whichspecific networking device you connect to,

Strany 15 - Getting Started

12 ADAM-4577 User’s Manual2.2 Connecting the HardwareNext, we will explain how to find a proper location for your EDG seriesand explain how to co

Strany 16 - 2.1 Understanding ADAM-4577

Chapter 2 Getting Started 13Figure 2-7 Panel Mounting

Strany 17 - Internet

14 ADAM-4577 User’s ManualFigure 2-8 Din Rail MountingDIN Rail MountingYou can mount the ADAM-4577 on a standard DIN Rail. First, usingtwo screws,

Strany 18 - 8 ADAM-4577 User’s Manual

Chapter 2 Getting Started 15Piggyback StackADAM-4577 can be stacked as seen in the figure below.Figure2-9 Piggyback Stack

Strany 19 - 2.1.3 Top / Front / Rear View

16 ADAM-4577 User’s Manual2.2.3 Power ConnectionYou should take the following steps to connect ADAM-4577 power.1.Connect the power cable to 2-pin c

Strany 20 - +Vs GNDPort1

Chapter 2 Getting Started 17Figure 2-12 Serial Connection for ADAM-4577ADAM-4577orFigure 2-11 Power Connection for ADAM-4577up , indicating that

Strany 21 - 2.1.4 Stickers

18 ADAM-4577 User’s ManualDB-9 (male)RS-232RS-485RS-422

Strany 22 - 2.2 Connecting the Hardware

Chapter 2 Getting Started 192.2.4.2 Connecting to PCSometimes, you want ADAM-4577 to connect to PC. You have to plugcrossed null modem connector

Strany 23 - Figure 2-7 Panel Mounting

Advantech Customer ServicesEach and every Advantech product is built to the most exactingspecifications to ensure reliable performance in the unusual

Strany 24 - DIN Rail Mounting

20 ADAM-4577 User’s Manual

Strany 25 - Piggyback Stack

3Installation andConfigurationChapter

Strany 26 - Ethernet

22 ADAM-4577 User’s Manual3.1 Windows utility InstallationThe ADAM-4577 provides two window-based utilities. One is configu-ration utility; the othe

Strany 27

Chapter 3 Installation and Configuration 233.2 Configuring the ADAM-4577The ADAM-4577 provides easy Windows configuration throughEthernet connect

Strany 28 - DB-9 (male)

24 ADAM-4577 User’s Manual3.2.1 Search for Specific ADAM-4577If you want to locate specific ADAM-4577s, the configuration utilityprovides a “Locate”

Strany 29 - 2.2.4.2 Connecting to PC

Chapter 3 Installation and Configuration 25Figure 3-3 Locate specific ADAM-4577sConfiguration utility can only search the ADAM-4570/4571/4572/457

Strany 30 - 20 ADAM-4577 User’s Manual

26 ADAM-4577 User’s ManualFirmware versionIn this field, the configuration utility represents the firmware version ofthe ADAM-4577. You might need t

Strany 31 - Configuration

Chapter 3 Installation and Configuration 273.2.2 Network ConfigurationThis section will show network configuration of ADAM-4577’sconfiguration ut

Strany 32 - 22 ADAM-4577 User’s Manual

28 ADAM-4577 User’s ManualTCP/IP:IP address, Subnet Mask, Default GatewayThe IP address identifies your ADAM-4577 device on the globalnetwork. Each

Strany 33 - 3.2 Configuring the ADAM-4577

Chapter 3 Installation and Configuration 293.2.3 Port ConfigurationFigure 3-5 Port Configuration WindowNameADAM-4577 provide one port to connecte

Strany 34 - 24 ADAM-4577 User’s Manual

Product WarrantyAdvantech warrants to you, the original purchaser, that each of itsproducts will be free from defects in materials and workmanship for

Strany 35 - Device Description

30 ADAM-4577 User’s ManualFlow ControlThe ADAM-4577 provides one option: NoneData BitsThe ADAM-4577 provides four options: 5, 6, 7 or 8.Stop BitsThe

Strany 36 - Firmware version

Chapter 3 Installation and Configuration 313.2.4 Setting ConfigurationADAM-4577 provides TCP/IP and UDP two protocol. In settings, youcan choose

Strany 37 - Ethernet:

32 ADAM-4577 User’s Manual3.2.4.1 TCP(UDP) Port numberThe TCP(UDP) port number represents the source port number , andthe number is used to identify

Strany 38 - 28 ADAM-4577 User’s Manual

Chapter 3 Installation and Configuration 333.2.4.2 Only configure the authorized IPThis option is enabled in order toprotect all configuration se

Strany 39 - 3.2.3 Port Configuration

34 ADAM-4577 User’s Manual3.2.4.5 Port Mode1. Selected PortThe default is Port1, DAM-4577 provide one port to connected tothe serial device.2. Port

Strany 40 - 30 ADAM-4577 User’s Manual

Chapter 3 Installation and Configuration 353.2.4.6 Protocol for CommunicationIn this option, you can choose either TCP or UDP mode according toy

Strany 41 - 3.2.4 Setting Configuration

36 ADAM-4577 User’s ManualTCP port of ADAM-4577: &&&&TCP port of ADAM-4577’s port1: &&&& +1For example:TCP port of A

Strany 42 - 3.2.4.1 TCP(UDP) Port number

Chapter 3 Installation and Configuration 37Figure 3-8 ADAM-4577 transmits data and response timeout diagramA: Time for Host PC transmits the data

Strany 43 - UDP Mode

38 ADAM-4577 User’s Manual2. Inter Frame BreakADAM-4577 provides one smart way to reduce inefficient waitingtime.Through Inter Frame Break,ADAM-4577

Strany 44 - 3.2.4.5 Port Mode

Chapter 3 Installation and Configuration 39Case2 :Assume the transmitted data spends 600 msAs Setting:Response timeout = 1000 msInter Frame Break

Strany 45

product returned without dated proof of purchase is not eligible forwarranty service.5. Write the RMA number visibly on the outside of the package and

Strany 46 - 36 ADAM-4577 User’s Manual

40 ADAM-4577 User’s Manual3.3 Testing UtilityThe purpose of testing utility is to help you diagnose the communica-tion between devices and download

Strany 47

Chapter 3 Installation and Configuration 413.3.1 Self Test FunctionThe purpose of this test is to confirm the communication from host PCto the AD

Strany 48 - 400 ms600 ms

42 ADAM-4577 User’s Manual3. If the connection is ok, click “Test” buttonCommunication Parameters Test• Baud rate: From 50 bps to 230 Kbps• Data bit

Strany 49 - Inter Frame Break

Chapter 3 Installation and Configuration 433.3.2 Upgrading ADAM-4577 (tm) s FirmwareDownloadAdvantech continually upgrades its firmware to keep p

Strany 50 - 3.3 Testing Utility

44 ADAM-4577 User’s Manual3.3.3 UDP Testing UtilityThe utility is for testing the status of ADAM-4577 UDP mode.By the utility, you can set Command T

Strany 51 - 3.3.1 Self Test Function

Chapter 3 Installation and Configuration 45Target Device & UDP PortYou can set Target Device IP Address according to Network IPAddress in Con

Strany 52 - 42 ADAM-4577 User’s Manual

46 ADAM-4577 User’s ManualThe command edit control can be inputted in ASCII code ast chooseASCII Command Forma, and the command edit control can be

Strany 53 - Download

Chapter 3 Installation and Configuration 47Send Command to the [IP Address : UDP Port] TimeoutFigure 3-13 Timeout FrameFollowing Frame is UDP Tes

Strany 54 - UDP network architecture

48 ADAM-4577 User’s ManualFigure 3-15 Command HEX Testing Windows

Strany 55 - Command Format

Chapter 3 Installation and Configuration 493.4 Status MessagesThe status message shown at the bottom of the utility window reflectsthe current st

Strany 56 - Command Timeout

ContentsChapter 1: Overview ... 11.1 Introduction...

Strany 57 - Figure 3-13 Timeout Frame

50 ADAM-4577 User’s Manual

Strany 58 - 48 ADAM-4577 User’s Manual

4Network Architectureand Example CodeChapter

Strany 59 - 3.4 Status Messages

52 ADAM-4577 User’s ManualADAM-4577 is one port universal series device which supprots TCP/UDP protocol. TCP mode applies to Polling, Event-handling

Strany 60 - 50 ADAM-4577 User’s Manual

Chapter 4 Network Architecture and Example Code 53Figure 4-2 Flow chart-Polling networkFigure 4-3 Polling Setting Windows Host PC creates TCP so

Strany 61 - Network Architecture

54 ADAM-4577 User’s ManualExample:SOCKADDR_IN Dst4577Addr;SOCKET Dst4577Sock;char RxData[10];memset(&Dst4577Addr, 0, sizeof(SOCKADDR_IN));Dst457

Strany 62 - 4.1 TCP Mode

Chapter 4 Network Architecture and Example Code 554.1.2 Event-handling Network ArchitectureIf an event occurs from serial devices connected to th

Strany 63 - Addr & TCP Port option

56 ADAM-4577 User’s ManualFigure 4-5 Flow chart-Event handling networkFigure 4-6 Event handling Setting Windows Define the TCP port of Host PC Ac

Strany 64 - 54 ADAM-4577 User’s Manual

Chapter 4 Network Architecture and Example Code 57Example:SOCKADDR_IN HostAddr;SOCKET HostSock;SOCKADDR_IN ClntAddr;SOCKET ClntSock;int ClntAddrL

Strany 65

58 ADAM-4577 User’s Manual4.1.3 Peer-to-peer Network ArchitectureIf you want to transmit data from one serial device to another serialdevice via the

Strany 66

Chapter 4 Network Architecture and Example Code 59Figure 4-9 Flow chart- Peer-to-peer network Complete the settings of #1 ADAM-4577 Key-in infor

Strany 67

3.2.4.1 TCP(UDP) Port number ... 323.2.4.2 Only configure the authorized IP ... 3

Strany 68

60 ADAM-4577 User’s ManualExample:1. Complete the settings of #1 ADAM-4577#1 ADAM-4577Module name: OfficeIP address: 172.18.1.198TCP port: 5200Figur

Strany 69

Chapter 4 Network Architecture and Example Code 612. Find out the IP address and TCP port of #2 ADAM-4577 that youwant to connect.#2 ADAM-4577Mod

Strany 70 - 60 ADAM-4577 User’s Manual

62 ADAM-4577 User’s Manual3. Key-in the IP address & TCP port of #2 ADAM-4577 in #1 ADAM-4577 configuration utility.Figure 4-12 Key-in the info

Strany 71

Chapter 4 Network Architecture and Example Code 634.2 UDP Mode4.2.1 Polling Network ArchitectureIn UDP Mode, If you want to use host PC to poll

Strany 72 - 62 ADAM-4577 User’s Manual

64 ADAM-4577 User’s ManualFigure 4-16 UDP Polling Setting WindowsExample:WSADATA wsd;SOCKADDR_IN Dst4577Addr;SOCKADDR_IN RecvedAddr;SOCKET Dst4577

Strany 73 - 4.2 UDP Mode

Chapter 4 Network Architecture and Example Code 65//|//+--Indicate the IP Address of ADAM4577 which you want to accessDst4577Addr.sin_port = hton

Strany 74 - 64 ADAM-4577 User’s Manual

66 ADAM-4577 User’s Manual

Strany 75

FiguresFigure 2-1 Network architecture: Polling ..... 7Figure 2-2 Network architecture: Event-handling .

Strany 76 - 66 ADAM-4577 User’s Manual

Figure 4-1 Network architecture-Polling ............. 52Figure 4-2 Flow chart-Polling network ......