Remote DA&C Modules
13-24
All product specifications are subject to change without notice Last updated : January 2005
Specifications
Counter Input
Channels Two independent 32-bit
counters
Input Frequency 50 kHz max.
Input Mode lsolated or non-isolated
Isolation Input Level Logic level 0: +1 V max.
Logic level 1: +3.5 V ~
+30 V
Isolation Voltage 2500 V
RMS
Non-isolated Programmable
threshold:
Input Level Logic level 0: 0 to +5 V
(default = 0.8 V)
Logic level 1: 0 to +5 V
(default = 2.4 V)
Input Pulse Width >10 ms.
Maximum Count 4,294,967,295 (32 bits)
Programmable Digital 2 ~ 65 ms
Noise Filter
Alarm Alarm comparator on
each counter
Preset Type Absolute or relative
Frequency Measurement
Range 5 Hz ~ 50 kHz
Programmable Built-in 1.0/0.1 sec.
Gate Time
Display (ADAM-4080D Only)
LED Indicator 5-digit readout,
CH 0 or CH 1
(programmable)
Digital Output
Channels 2
Open collector to 30 V,
30 mA max. load
power dissipation: 300
mW for each channel
Built-in Watchdog Timer
Power
Power Requirements Unregulated 10~30 V
DC
Power Consumption 2.0 W @ 24 V
DC
ADAM-4914V
8-channel Power Relay Output Module with Modbus
®
Counter/Frequency Module
Counter/Frequency Module with LED Display
4-channel Voltage Input Surge Protection Module
ADAM-4069
ADAM-4080
ADAM-4080D
ADAM-4914V
ADAM-4080/4080D
NEW
Ordering Information
ADAM-4914V 4-channel Voltage Input
Surge Protection Module
ADAM-4080 Counter/Frequency Module
ADAM-4080D Counter/Frequency Module
with LED Display
Specifications
Input
Channels 4 differential voltage
input and thermocouple
Performance
Discharge Voltage BETWEEN LINES: 18 V
min
LINE TO GND: 350 V
max.
Max. Surge Voltage BETWEEN LINES: 23 V
min
LINE TO GND: +4,000 V
max.
Leakage Current BETWEEN LINES: ≤
10µA @ 7.5 V
DC
LINE TO GND: ≤ 5µA @
+140 V
DC
Response Time ≤ 0.1 µsec.
Discharge Current 5,000 A (8/20 µsec.)
Internal Series Approx. 20Ω including
Resistance return
Maximum Line Voltage 10 V
ADAM-4069
Specifications
Relay Output
Channels 8 form A
Contact Rating AC: 250 V @ 5 A
DC: 30 V @ 5 A
Breakdown Voltage 1000 V
AC
(50/60 Hz)
Relay on Time (typical) 5 ms
Relay off Time (typical) 5.6 ms
Insulation Resistance 1,000 MΩ minimum at
500 V
DC
Built-in Watchdog System and Comm.
Timer Watchdog
Power
Power Requirements Unregulated
+10 ~ +30 V
DC
Power Consumption 0.6 W @ 24 V
DC
Ordering Information
ADAM-4069 8-channel Power Relay
Output Module with
Modbus
®