4-82 ADAM 4000 Series User's Manual
Command Set
4014D
$AA6(data_A)(data_B)
Name Write Source High/Low Values for Linear Mapping
Description Write the high/low limit values to a specified module for linear
mapping. The module will only activate the source values after
new target high/low values are written (Command $AA7).
Syntax $AA6(data_A)(data_B)(cr)
$ is a delimiter character.
AA (range 00-FF) represents the 2-character hexadecimal
address of the analog input module.
6 identifies the set high/low limit value for linear mapping
command.
(data_A) is the low limit input value of the module for linear
mapping. This value must be lower than the modules high
limit input value for linear mapping (data_B). The data format
is the same as the modules input current range. The minimum
value allowed is equal to the minimum input value of the
current range.
(data_B) is the high limit input value of the module for linear
mapping. This value must be greater than the modules low
limit input value for linear mapping (data_A). The data format
is the same as the modules input current range, and the
maximum value allowed is equal to the maximum input value
of the current range.
(cr) is the terminating character, carriage return (0Dh)
Response !AA(cr) if the command is valid.
The addressed module stores the high/low input values in a
buffer. The module updates these values only after the com-
mand $AA7(data_C) (data_D) is executed.
?AA(cr) if an invalid operation was entered.
There is no response if the module detects a syntax error or
communication error or if the specified address does not exist.
? is a delimiter character indicating the command was invalid.
AA (range 00-FF) represents the 2-character hexadecimal
address of an analog input module.
(cr) is the terminating character, carriage return (0Dh).
Zobrazit stránku 165
1 2 ... 161 162 163 164 165 166 167 168 169 170 171 ... 397 398

Komentáře k této Příručce

Žádné komentáře

ETC Unison Heritage Contact and Fader Interface Handbücher

Bedienungsanleitungen und Benutzerhandbücher für Schalttafel ETC Unison Heritage Contact and Fader Interface.
Wir stellen 1 PDF-Handbücher ETC Unison Heritage Contact and Fader Interface zum kostenlosen herunterladen nach Dokumenttypen zur Verfügung Bedienungsanleitung






Weitere Produkte und Handbücher für Schalttafel ETC

Modelle Dokumententyp
Unison Heritage Rackmount Contact Interface Bedienungsanleitung   ETC Unison Heritage Rackmount Contact Interface User Manual, 3 Seiten
Unison Heritage Consolette Station Bedienungsanleitung   ETC Unison Heritage Consolette Station User Manual, 1 Seiten
Unison Heritage Fader Station Bedienungsanleitung   ETC Unison Heritage Fader Station User Manual, 4 Seiten