Advantech Data Acquisition Modules ADAM 4000 Uživatelský manuál Strana 258

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 429
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 257
Chapter 7
7-
23
ADAM 4000 Series User’s Manual
$AAE0
Name Read and Clear over Current Status Flag command
Description Read the Over Current Status Flag and Clear the Flag
simultaneously.
Syntax $AAE0(cr)
$ is a delimiter character.
AA (range 00-FF) represents the 2-character hexadecimal
address that you will access to.
E0 is the Read and Clear over Current Status Flag command.
(cr) is the terminating character, carriage return (ODh).
Response !AAX(cr): if the command is valid.
?AA(cr): if an invalid command has been issued.
X is one-hexadecimal character (range from 0 to 7)
X=0: No over current occur
X=1: DO0~3 has over current occurred
X=2: DO4~7 has over current occurred
X=4: DO8~11 has over current occurred
! is a delimiter character which indicates a valid command
? is a delimiter character which indicates an invalid command
(cr) is the terminating character, carriage return (ODh).
4056SO
Zobrazit stránku 257
1 2 ... 253 254 255 256 257 258 259 260 261 262 263 ... 428 429

Komentáře k této Příručce

Žádné komentáře