Smart Web Ethernet I/O Modules
15-16
All product specifications are subject to change without notice Last updated : January 2005
6 DI/6 Relay Module
6 DI/6 Power Relay Module
7-channel RTD Module
Channels 12
I/O Type 6 Relay & 6 DI
Relay Output (Form A) Contact Rating:
AC: 120 V @ 0.5 A
DC: 30 V @ 1 A
Breakdown voltage: 500
V
AC
(50/60 Hz)
Relay on time: 7 ms
Relay off time: 3 ms
Total switching time:
10 ms
Insulation resistance:
1000 MΩ minimum at
500V
DC
Digital Input Dry Contact:
Logic level 0: close to
GND
Logic level 1: open
Wet Contact:
Logic level 0: +3Vmax
Logic level 1:
+10 V to 30 V
DC
Optical Isolation 2000V
RMS
Power Consumption 2 W (Typical)
Channels 7 differential
Effective Resolution 16-bit
Input Type Pt, Balco and Ni RTD
RTD Types and Temperature Ranges
PT-100 RTD
Pt-50° C to 150° C
Pt 0° C to 100° C
Pt 0° C to 200° C
Pt 0° C to 400° C
Pt-200° C to 200° C
IEC RTD 100 ohms.= 0.00385)
JIS RTD 100 ohms.= 0.00392)
Pt 1000 RTD
Pt -40° C to 160° C
Balco 500 RTD
-30° C to 120° C
Ni 50 RTD
100° C
Ni 508 RTD
Ni 0° C to 100° C
Isolation Voltage 2000 V
DC
Sampling Rate 10 samples / sec.
Input Impedance 10 kΩ
Input Connections 2 or 3 wire
Accuracy ± 0.05 % or better
Zero Drift ± 3 µV/° C
Span Drift ± 25 ppm/° C
CMR @ 50/60 Hz 150 dB
NMR @ 50/60 Hz 100 dB
Built-in Watchdog Timer
Individual Wire Burn-out Detection
Power Requirements Unregulated
+10 ~ +30 V
DC
Power Consumption 2 W
ADAM-6060
ADAM-6066
ADAM-6015
ADAM-6060 ADAM-6015
Specifications
Ordering Information
ADAM-6060 6 Isolated Digital Inputs
& 6 Relays Module
Specifications
Ordering Information
ADAM-6015 7-channel RTD Input
Module
NEW
ADAM-6066
Channels 12
I/O Type 6 Relay & 6 DI
Relay Output (Form A) Contact Rating:
AC: 250 V @ 5 A
DC: 30 V @ 5 A
Breakdown voltage: 500
V
AC
(50/60 Hz)
Relay on time: 7 ms
Relay off time: 3 ms
Total switching time:
10 ms
Insulation resistance:
1000 MΩ minimum at
500V
DC
Digital Input Dry Contact:
Logic level 0: close to
GND
Logic level 1: open
Wet Contact:
Logic level 0: +3Vmax
Logic level 1:
+10 V to 30 V
DC
Optical Isolation 2000V
RMS
Power Consumption 2.5 W (Typical)
Specifications
Ordering Information
ADAM-6066 6 Isolated Digital Inputs
& 6 Power Relays
Module
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com